Three-phase O-PEN® connection centres for commercial EV charging infrastructure. Standardise your installations, eliminate groundworks, and remain fully BS 7671 compliant.

Three-Phase Protection for Commercial Sites

Our commercial connection centres incorporate the patented O-PEN® device for three-phase PME supply installations. When an open PEN condition is detected, the system automatically isolates the supply or individual loads, preventing dangerous touch voltages from exceeding 70V RMS.

Designed for large commercial EV charging infrastructure, these units standardise your installation process across charge points while eliminating the need for service location scanning and minimising civil works requirements.

1250A
Max Supply
Three-Phase
Supply Type
<70V RMS
Touch Voltage
BS 7671:2018
Standard
EV charging in a commercial car park
Commercial EV three-phase connection centre

Key Benefits

No Service Location Scanning

Eliminates the need for buried service scanning before installation, saving time and cost on every job.

Minimal Civil Works

No need for earth electrodes or complex groundworks. Direct connection to PME supply with consistent earth resistance year-round.

Metal Structure Compatible

Units can be mounted directly on metal-clad structures without additional earthing requirements.

Standardised Process

Provides a consistent, repeatable installation procedure across all charge points, reducing error and training requirements.

Automatic Fault Isolation

Open PEN conditions are detected and isolated automatically, protecting users from dangerous touch voltages.

Made in Great Britain

Designed and manufactured in the UK to exacting quality standards.

Available Units

Manual Reset

EVU Connection Centres

Three-phase connection centre with manual reset capability. Ideal for installations requiring manual intervention after fault clearance.

  • Three-phase O-PEN® protection
  • Manual reset post-fault
  • Up to 1250A
  • PME direct connection
Auto Reset

ARD Connection Centres

Auto-reset variant for installations where automatic restoration of supply after fault clearance is required.

  • Three-phase O-PEN® protection
  • Automatic reset
  • Up to 1250A
  • PME direct connection
Specialist Unit

MTE A 5P

Specialist 5-pole protection unit for specific commercial installation configurations requiring enhanced protection.

  • 5-pole protection
  • Three-phase + N + PE
  • Specialist applications
  • BS 7671 compliant

Compliance & Standards

All commercial units comply with BS:7671 2018: Amendment 2: 2022, Regulation 722.411.4.1 (iii)